Technical Properties
Architecture
![]() | Type of order: | Not applicable |
![]() | Number of poles: | 4 P |
Main electrical features
![]() | Frequency: | 50 Hz |
![]() | Rated operational voltage Ue: | 400 V |
Voltage
![]() | Rated insulation voltage: | 440 V |
![]() | Command voltage AC: | 230 V |
![]() | Rated impulse withstand voltage: | 4 kV |
Electric current
![]() | Acceptable current load with AC7 category A: | 63 A |
![]() | Acceptable current load with AC7 category B: | 32 A |
![]() | Thermal rated current outside of housings: | 63 A |
Power
![]() | Inrush power absorbed: | 62,5 W |
![]() | Operating consumption: | 5,75 W |
![]() | Contact rating with 230 V in AC7 category A: | 11,6 kW |
![]() | Contact rating with 230 V in AC7 category B: | 3,3 kW |
![]() | Contact rating with 400 V in AC7 category A: | 35 kW |
![]() | Contact rating with 400 V in AC7 category B: | 7,8 kW |
![]() | Power loss per contact: | 5 W |
![]() | Total power loss under IN: | 25,75 W |
![]() | Power dissipation per coil: | 0,5 W |
Tripping
![]() | Time of response when closing: | 25 ms |
![]() | Time of response when opening: | 20 ms |
Resistance
![]() | Winding resistance: | 770 Ω |
Endurance
![]() | Electric endurance in number of cycles: | 30000 |
![]() | Number of mechanical operations: | 1000000 |
Dimensions
![]() | Depth of installed product: | 60 mm |
![]() | Height of installed product: | 85 mm |
![]() | Width of installed product: | 54 mm |
Fluorescent bulbs control
![]() | Max. load fluorescent lamp: | 3000 VA |
![]() | Max. power with fluorescent parallel lamps: | 2100 VA |
![]() | Fluorescent lamps in duo circuit: | 4700 VA |
Incandescent bulbs control
![]() | Max. power with incandescent lamps: | 6500 W |
Installation, mounting
![]() | Tightening torque: | Coil: 2,5Nm, Power: 3,5Nm |
Connection
![]() | Connection cross-sect. rigid cable: | 4 /25mm² |
![]() | Connection cross-sect. flexible conductor: | 4 / 16mm² |
![]() | Type of connection: | with screw |
![]() | Number of contacts: | 4 |
![]() | Type of contacts: | 2NC+2NO |
Equipment
![]() | Can be accessorized: | yes |
Use
![]() | Local operation/hand operation: | no |
Standards
![]() | European directive WEEE: | concerned |
Safety
![]() | Protection class: | isol.class II |
![]() | Protection index IP: | IP2X |
Use conditions
![]() | Operating temperature: | -10 … 50 °C |
![]() | Storage/transport temperature: | -40 … 80 °C |
*All data is subject to errors and technical modifications. All prices are recommended retail prices.