Technical Properties
Main electrical features
| Frequency: | 50/60 Hz | |
| Type of supply voltage: | AC/DC | |
| Rated operational voltage Ue: | 230/415 V |
Voltage
| Rated insulation voltage: | 4000 V | |
| Command voltage AC: | 230/415 V | |
| DC control voltage: | 110/130 V | |
| Rated operational voltage in DC: | 110/130 V |
Electric current
| Imin = f (U = 230 V AC): | 14 mA | |
| Imin=f(U=415V AC) for power circuit: | 32 mA |
Power
| Inrush power absorbed: | 15 VA | |
| Total power loss under IN: | 25,3 W |
Tripping
| Time of response when opening: | 200 ms |
Dimensions
| Depth of installed product: | 68 mm | |
| Height of installed product: | 83 mm | |
| Width of installed product: | 18 mm |
Installation, mounting
| Tightening torque: | 1,2Nm |
Connection
| Connection cross-sect. rigid cable: | 10mm² | |
| Connection cross-sect. flexible conductor: | 6mm² |
Standards
| European directive WEEE: | concerned |
Use conditions
| Storage temperature: | -40 to 80 °C | |
| Air humidity protection: | 95% |
*All data is subject to errors and technical modifications. All prices are recommended retail prices.