Cat. Ref.:NT104C
EAN No.:3250614806933
ex. GST*:22,39 $ / pc.
inc. GST*:24,63 $ / pc.

Technical Properties

Architecture
Number of protected poles:1
Number of poles:1 P
Type of pole:1 P
Fixing mode:DIN rail type O
(symmetrical)
Curve:C
Functions
Concurrently switching N-neutral:no
Connectivity
Top connection alignement for modular devices:Aligned terminal
Bottom connection alignement for modular devices:Aligned terminal
Main electrical features
Rated short circuit breaking capacity Icn AC according IEC60898-1:10 kA
Rated operational voltage Ue:240 / 415 V
Type of supply voltage:AC
Frequency:50/60 Hz
Voltage
Rated insulation voltage:500 V
Rated impulse withstand voltage:4000 V
Electric current
Rated current:4 A
Rated service breaking capacity Ics AC according IEC 60898-1:7,5 kA
min/maxi threshold value of the AC thermal operation:1,13 / 1,45 In
Magnetic regulating currrent:5 / 10 In
Rated short circuit breaking capacity Icn under 230V AC according IEC60898-1:10 kA
Rated short circuit breaking capacity Icn under 240V AC according IEC 60898-1:10 kA
Rated service breaking capacity Ics under 230V AC according IEC 60898-1:7,5 kA
Rated service breaking capacity Ics under 240V AC according IEC 60898-1:7,5 kA
Electric current / temperature
Rating current -25°C:4,4 A
Rating current -20°C:4,4 A
Rating current -15°C:4,3 A
Rating current -10°C:4,3 A
Rating current -5°C:4,3 A
Rating current 0°C:4,2 A
Rating current 5°C:4,2 A
Rating current 10°C:4,2 A
Rating current 15°C:4,1 A
Rating current 20°C:4,1 A
Rating current 25°C:4 A
Rating current 30°C:4 A
Rating current 35°C:4 A
Rating current 40°C:3,9 A
Rating current 45°C:3,9 A
Rating current 50°C:3,8 A
Rating current 55°C:3,8 A
Rating current 60°C:3,8 A
Rating current 65°C:3,7 A
Rating current 70°C:3,7 A
Current correction factors
Correction factor of rating current for 2 devices placed side-by-side:1
Correction factor of rating current for 3 devices placed side-by-side:0,95
Correction factor of rating current for 4 and 5 devices placed side-by-side:0,9
Correction factor of rating current for 6 devices placed side-by-side:0,85
Correction factor of magnetic tripping with 100 Hz:1,1
Correction factor of magnetic tripping with 200 Hz:1,2
Correction factor of magnetic tripping with 400 Hz:1,5
Correction factor of magnetic tripping with 60 Hz:1
Frequency
Frequency:50 to 60 Hz
Power
Total power loss under IN:1,9 W
Power loss per pole at In:1,9 W
Endurance
Electric endurance in number of cycles:4000
Number of mechanical operations:20000
Dimensions
Depth of installed product:70 mm
Height of installed product:83 mm
Width of installed product:17,5 mm
Installation, mounting
Type of top connection for modular devices:with screw
Tightening torque:2,8Nm
Type of top rail clip for modular devices:NA
Type of bottom rail clip for modular devices:metallic isolated
Type of Bottom Connection for modular devices:BIconnect
Top removability for modular devices:no
Bottom removability for modular devices:no
360° product mounting position:yes
Connection
Connection cross-section of input and output with screws, for massive conductors:1 / 35 mm²
Connection cross section of access and exit with screws, for flexible conductor:1 / 25 mm²
Type of connection:with screw
Standards
Standard text:IEC 60898-1, AS/NZS
60898-1
Safety
Protection index IP:IP20
Use conditions
Operating temperature:-25…70 °C
Degree of pollution according to IEC 60664 / IEC 60947-2:2
Class of energy limitation I²t:3
Altitude:2000 m
Air humidity protection:for all climates
Storage/transport temperature:-25…80 °C