Technical Properties
Architecture
![]() | Number of protected poles: | 1 |
![]() | Number of poles: | 1 P |
![]() | Type of pole: | 1 P |
![]() | Fixing mode: | DIN rail type O (symmetrical) |
![]() | Curve: | C |
Connectivity
![]() | Bottom connection alignement for modular devices: | Aligned terminal |
![]() | Top connection alignement for modular devices: | Aligned terminal |
Main electrical features
![]() | Frequency: | 50/60 Hz |
![]() | Rated short circuit breaking capacity Icn AC according IEC60898-1: | 10 kA |
![]() | Type of supply voltage: | AC |
![]() | Rated operational voltage Ue: | 240/415 V |
Voltage
![]() | Rated insulation voltage: | 500 V |
![]() | Rated impulse withstand voltage: | 4000 V |
Electric current
![]() | Rated short circuit breaking capacity Icn under 230V AC according IEC60898-1: | 10 kA |
![]() | Rated short circuit breaking capacity Icn under 240V AC according IEC 60898-1: | 10 kA |
![]() | Rated service breaking capacity Ics AC according IEC 60898-1: | 7,5 kA |
![]() | Rated service breaking capacity Ics under 230V AC according IEC 60898-1: | 7,5 kA |
![]() | Rated service breaking capacity Ics under 240V AC according IEC 60898-1: | 7,5 kA |
![]() | Magnetic regulating currrent: | 5/10 In |
![]() | min/maxi threshold value of the AC thermal operation: | 1,13/1,45 In |
Electric current / temperature
![]() | Rating current -15°C: | 31 A |
![]() | Rating current -20°C: | 31,6 A |
![]() | Rating current 0°C: | 29,1 A |
![]() | Rating current 10°C: | 27,8 A |
![]() | Rating current -10°C: | 30,4 A |
![]() | Rating current 15°C: | 27,1 A |
![]() | Rating current 20°C: | 26,4 A |
![]() | Rating current 25°C: | 25,7 A |
![]() | Rating current -25°C: | 32,2 A |
![]() | Rating current 30°C: | 25 A |
![]() | Rating current 35°C: | 24,2 A |
![]() | Rating current 40°C: | 23,5 A |
![]() | Rating current 45°C: | 22,7 A |
![]() | Rating current 5°C: | 28,5 A |
![]() | Rating current -5°C: | 29,8 A |
![]() | Rating current 50°C: | 21,8 A |
![]() | Rating current 55°C: | 21 A |
![]() | Rating current 60°C: | 20 A |
![]() | Rating current 65°C: | 19,3 A |
![]() | Rating current 70°C: | 18,4 A |
Current correction factors
![]() | Correction factor of magnetic tripping with 100 Hz: | 1,1 |
![]() | Correction factor of magnetic tripping with 200 Hz: | 1,2 |
![]() | Correction factor of magnetic tripping with 400 Hz: | 1,5 |
![]() | Correction factor of magnetic tripping with 60 Hz: | 1 |
![]() | Correction factor of rating current for 2 devices placed side-by-side: | 1 |
![]() | Correction factor of rating current for 3 devices placed side-by-side: | 0,95 |
![]() | Correction factor of rating current for 4 and 5 devices placed side-by-side: | 0,9 |
![]() | Correction factor of rating current for 6 devices placed side-by-side: | 0,85 |
Power
![]() | Power loss per pole at In: | 3 W |
![]() | Total power loss under IN: | 3 W |
Endurance
![]() | Electric endurance in number of cycles: | 4000 |
![]() | Number of mechanical operations: | 20000 |
Dimensions
![]() | Depth of installed product: | 70 mm |
![]() | Height of installed product: | 83 mm |
![]() | Width of installed product: | 17,5 mm |
Installation, mounting
![]() | Type of top connection for modular devices: | with screw |
![]() | Tightening torque: | 2,8Nm |
![]() | Type of bottom rail clip for modular devices: | metallic isolated |
![]() | Type of top rail clip for modular devices: | NA |
![]() | Type of Bottom Connection for modular devices: | BIconnect |
![]() | Bottom removability for modular devices: | no |
![]() | Top removability for modular devices: | no |
Connection
![]() | Type of connection: | with screw |
![]() | Connection cross section of access and exit with screws, for flexible conductor: | 1/25 mm² |
![]() | Connection cross-section of input and output with screws, for massive conductors: | 1/35 mm² |
Standards
![]() | Standard text: | IEC 60898-1, AS/NZS 60898-1 |
Safety
![]() | Protection index IP: | IP20 |
Use conditions
![]() | Degree of pollution according to IEC 60664 / IEC 60947-2: | 2 |
![]() | Operating temperature: | -25 … 70 °C |
![]() | Class of energy limitation I²t: | 3 |
![]() | Altitude: | 2000 m |
![]() | Air humidity protection: | for all climates |
![]() | Storage/transport temperature: | -25 … 80 °C |