Cat. Ref.:NT150C
EAN No.:3250614807077
ex. GST*:21,52 $ / pc.
inc. GST*:23,67 $ / pc.

Technical Properties

Architecture
Number of protected poles:1
Number of poles:1 P
Type of pole:1 P
Fixing mode:DIN rail type O
(symmetrical)
Curve:C
Connectivity
Bottom connection alignement for modular devices:Aligned terminal
Top connection alignement for modular devices:Aligned terminal
Main electrical features
Frequency:50/60 Hz
Rated short circuit breaking capacity Icn AC according IEC60898-1:10 kA
Type of supply voltage:AC
Rated operational voltage Ue:240/415 V
Voltage
Rated insulation voltage:500 V
Rated impulse withstand voltage:4000 V
Electric current
Rated short circuit breaking capacity Icn under 240V AC according IEC 60898-1:10 kA
Rated service breaking capacity Ics AC according IEC 60898-1:7,5 kA
Rated service breaking capacity Ics under 240V AC according IEC 60898-1:7,5 kA
Magnetic regulating currrent at 40° C:5/10 In
min/maxi threshold value of the AC thermal operation:1,13/1,45 In
Electric current / temperature
Rating current -15°C:62,3 A
Rating current -20°C:63,5 A
Rating current 0°C:58,7 A
Rating current 10°C:56,1 A
Rating current -10°C:61,1 A
Rating current 15°C:54,7 A
Rating current 20°C:53,4 A
Rating current 25°C:52 A
Rating current -25°C:64,7 A
Rating current 30°C:50 A
Rating current 35°C:48,8 A
Rating current 40°C:47,7 A
Rating current 45°C:46,5 A
Rating current 5°C:57,4 A
Rating current -5°C:59,9 A
Rating current 50°C:45,3 A
Rating current 55°C:44,1 A
Rating current 60°C:43 A
Rating current 65°C:41,8 A
Rating current 70°C:40,6 A
Current correction factors
Correction factor of magnetic tripping with 100 Hz:1,1
Correction factor of magnetic tripping with 200 Hz:1,2
Correction factor of magnetic tripping with 400 Hz:1,5
Correction factor of magnetic tripping with 60 Hz:1
Correction factor of rating current for 2 devices placed side-by-side:1
Correction factor of rating current for 3 devices placed side-by-side:0,95
Correction factor of rating current for 4 and 5 devices placed side-by-side:0,9
Correction factor of rating current for 6 devices placed side-by-side:0,85
Power
Power loss per pole at In:5,2 W
Total power loss under IN:5,2 W
Endurance
Electric endurance in number of cycles:4000
Number of mechanical operations:20000
Dimensions
Depth of installed product:70 mm
Height of installed product:83 mm
Width of installed product:17,5 mm
Installation, mounting
Type of top connection for modular devices:with screw
Tightening torque:2,8Nm
Type of bottom rail clip for modular devices:metallic isolated
Type of top rail clip for modular devices:NA
Type of Bottom Connection for modular devices:BIconnect
Bottom removability for modular devices:no
Top removability for modular devices:no
Connection
Type of connection:with screw
Connection cross section of access and exit with screws, for flexible conductor:1/25 mm²
Connection cross-section of input and output with screws, for massive conductors:1/35 mm²
Equipment
Can be accessorized:yes
Standards
Standard text:IEC 60898-1, AS/NZS
60898-1
Safety
Protection index IP:IP20
Use conditions
Degree of pollution according to IEC 60664 / IEC 60947-2:2
Class of energy limitation I²t:3
Altitude:2000 m
Storage temperature:-25 to 80 °C
Air humidity protection:for all climates