Technical Properties
Architecture
| Neutral position: | without neutral | |
| Number of protected poles: | 1 | |
| Number of poles: | 1 P | |
| Type of pole: | 1 P | |
| Fixing mode: | Din-Rail | |
| Curve: | D |
Compatibility
| Compatible with DIN rail mounting: | yes |
Connectivity
| Bottom connection alignement for modular devices: | Aligned terminal | |
| Top connection alignement for modular devices: | Aligned terminal |
Main electrical features
| Type of supply voltage: | AC | |
| Rated operational voltage Ue: | 230/400 V |
Voltage
| Minimum threshold voltage (Ue min): | 12 V | |
| Rated insulation voltage: | 500 V | |
| Rated impulse withstand voltage: | 6000 V |
Electric current
| Rated short circuit breaking capacity Icn under 230V AC according IEC60898-1: | 10 kA | |
| Rated short circuit breaking capacity Icn under 240V AC according IEC 60898-1: | 10 kA | |
| Rated service breaking capacity Ics AC according IEC 60898-1: | 7,5 kA | |
| Rated service breaking capacity Ics under 220V AC according IEC 60947-2: | 7,5 kA | |
| Rated service breaking capacity Ics under 230V AC according IEC 60947-2: | 7,5 kA | |
| Rated service breaking capacity Ics under 240V AC according IEC 60947-2: | 7,5 kA | |
| Rated service breaking capacity Ics under 220V AC according IEC 60898-1: | 7,5 kA | |
| Rated service breaking capacity Ics under 230V AC according IEC 60898-1: | 7,5 kA | |
| Rated service breaking capacity Ics under 240V AC according IEC 60898-1: | 7,5 kA | |
| Rated ultimate short-circuit breaking capacity Icu under 220V AC IEC 60947-2: | 15 kA | |
| Rated ultimate short-circuit breaking capacity Icu under 230V AC IEC 60947-2: | 15 kA | |
| Rated ultimate short-circuit breaking capacity Icu under 240V AC IEC 60947-2: | 15 kA | |
| Magnetic regulating currrent at 40° C: | 10/14,4 In | |
| min/maxi threshold value of the DC magnetic operation: | 15/30 In | |
| min/maxi threshold value of the AC thermal operation: | 1,13/1,45 In | |
| min/maxi threshold value of the DC thermal operation: | 1,13/1,45 In |
Electric current / temperature
| Rating current -15°C: | 12,39 A | |
| Rating current -20°C: | 12,63 A | |
| Rating current 0°C: | 11,65 A | |
| Rating current 10°C: | 11,13 A | |
| Rating current -10°C: | 12,15 A | |
| Rating current 25°C: | 10,29 A | |
| Rating current -25°C: | 12,86 A | |
| Rating current 30°C: | 10 A | |
| Rating current 35°C: | 9,7 A | |
| Rating current 40°C: | 9,39 A | |
| Rating current 45°C: | 9,06 A | |
| Rating current 5°C: | 11,39 A | |
| Rating current -5°C: | 11,9 A | |
| Rating current 50°C: | 8,73 A | |
| Rating current 55°C: | 8,38 A | |
| Rating current 60°C: | 8,02 A | |
| Rating current 65°C: | 7,64 A | |
| Rating current 70°C: | 7,24 A | |
| Rating current 0°C according to IEC 60947-2: | 13,35 A | |
| Rating current 10°C according to IEC 60947-2: | 12,75 A | |
| Rating current -10°C according to IEC 60947-2: | 13,92 A | |
| Rating current 150°C according to IEC 60947-2: | 12,44 A | |
| Rating current -15°C according to IEC 60947-2: | 14,2 A | |
| Rating current 20°C according to IEC 60947-2: | 12,12 A | |
| Rating current -20°C according to IEC 60947-2: | 14,47 A | |
| Rating current 25°C according to IEC 60947-2: | 11,79 A | |
| Rating current -25°C according to IEC 60947-2: | 14,74 A | |
| Rating current 30°C according to IEC 60947-2: | 11,46 A | |
| Rating current 35°C according to IEC 60947-2: | 11,11 A | |
| Rating current 40°C according to IEC 60947-2: | 10,75 A | |
| Rating current 45°C according to IEC 60947-2: | 10,38 A | |
| Rating current 5°C according to IEC 60947-2: | 13,05 A | |
| Rating current -5°C according to IEC 60947-2: | 13,64 A | |
| Rating current 50°C according to IEC 60947-2: | 10 A | |
| Rating current 55°C according to IEC 60947-2: | 9,6 A | |
| Rating current 60°C according to IEC 60947-2: | 9,19 A | |
| Rating current 65°C according to IEC 60947-2: | 8,75 A | |
| Rating current 70°C according to IEC 60947-2: | 8,29 A |
Current correction factors
| Correction factor of magnetic tripping with 100 Hz: | 1,1 | |
| Correction factor of magnetic tripping with 200 Hz: | 1,2 | |
| Correction factor of magnetic tripping with 400 Hz: | 1,5 | |
| Correction factor of magnetic tripping with 60 Hz: | 1,1 | |
| Correction factor of rating current for 2 devices placed side-by-side: | 1 | |
| Correction factor of rating current for 3 devices placed side-by-side: | 0,95 | |
| Correction factor of rating current for 4 and 5 devices placed side-by-side: | 0,9 | |
| Correction factor of rating current for 6 devices placed side-by-side: | 0,85 |
Power
| Power loss per pole at In: | 1,87 W | |
| Maximum power loss per pole according to the product standard: | 3 W | |
| Total power loss under IN: | 1,87 W |
Endurance
| Electric endurance in number of cycles: | 4000 | |
| Number of mechanical operations: | 20000 |
Dimensions
| Depth of installed product: | 70 mm | |
| Height of installed product: | 83 mm | |
| Width of installed product: | 17,5 mm |
Installation, mounting
| Type of top connection for modular devices: | with screw | |
| Tightening torque: | 2,8Nm | |
| Type of bottom rail clip for modular devices: | plastic | |
| Type of top rail clip for modular devices: | NA | |
| Type of Bottom Connection for modular devices: | BIconnect | |
| Bottom removability for modular devices: | yes | |
| Top removability for modular devices: | yes | |
| Suitable for flush-mounting: | yes |
Connection
| Upstream cage clamp delivery status: | opened | |
| Downstream cage clamp delivery status: | opened | |
| Connection cross-section at output with screw, for flexible conductor: | 1/25 mm² | |
| Connection cross-section of the access with screws, with flexible conductor: | 1/25 mm² | |
| Connection cross-section at output with screw, for massive conductor: | 1/35 mm² | |
| Connection cross-section for rigid conductor, upstream terminals with screws: | 1/35 mm² |
Equipment
| Can be accessorized: | yes |
Standards
| Standard text: | EN 60898-1, IEC 60947-2 | |
| European directive WEEE: | concerned |
Safety
| Protection index IP: | IP20 |
Use conditions
| Degree of pollution according to IEC 60664 / IEC 60947-2: | 2 | |
| Altitude: | 2000 m | |
| Storage temperature: | -25 to 80 °C |
temperatur
| Temperature of calibration: | 50 °C |
*All data is subject to errors and technical modifications. All prices are recommended retail prices.