Cat. Ref.:HND630H
EAN No.:3250613349554
ex. GST*:3.389,10 $ / pc.
inc. GST*:3.728,01 $ / pc.

Technical Properties

Architecture
Type of order:Toggle
Number of poles:3 P
Type of pole:3P3D
Functions
Complete device with protection unit:yes
Trip Unit:LSI
Integrated earth fault protection:no
Compatibility
Compatible with DIN rail mounting:no
Main electrical features
Rated operational voltage Ue:220 / 690 V
Frequency:50/60 Hz
Voltage
Rated insulation voltage:800 V
Rated impulse withstand voltage:8 kV
With under voltage release:no
Electric current
Rated current:630 A
Rated ultimate short-circuit breaking capacity Icu under 690V AC IEC 60947-2:20 kA
Thermal protection nob setting xIN:0,4 / 0,5 / 0,63 / 0,8
/ 0,9 / 0,95 / 1
Breaking capacity on 1 pole for IT 230V NF 60947-2:51 kA
Breaking capacity on 1 pole for IT 400V NF 60947-2:9 kA
Rated service breaking capacity Ics AC according IEC 60947-2:100 %
Rated ultimate short-circuit breaking capacity Icu under 230V AC IEC 60947-2:85 kA
Rated ultimate short-circuit breaking capacity Icu under 240V AC IEC 60947-2:85 kA
Rated ultimate short-circuit breaking capacity Icu under 400V AC IEC 60947-2:50 kA
Rated ultimate short-circuit breaking capacity Icu under 415V AC IEC 60947-2:50 kA
Rated ultimate short-circuit breaking capacity Icu under 440V AC IEC 60947-2:45 kA
Current correction factors
Correction factor of rating current for 2 devices placed side-by-side:1
Correction factor of rating current for 3 devices placed side-by-side:1
Correction factor of rating current for 4 and 5 devices placed side-by-side:1
Correction factor of rating current for 6 devices placed side-by-side:1
Power
Total power loss under IN:120 W
Power loss per pole at In:40 W
Tripping
Tripmode:LSI
Thermal protection trip time:5 / 10 / 11 / 16 / 21
ms
Time of response when opening:10 ms
Electrical specifications
Magnetic trip delay time:100 to 200 ms
Endurance
Electric endurance in number of cycles:1000
Number of mechanical operations:4000
Installation, mounting
Tightening torque:22Nm
DIN rail mounting with optional adaptator:no
Connection
Connection cross-sect. flexible conductor:35 / 240mm²
Connection cross-sect. rigid cable:35 / 240mm²
Connection:Front connection
Type of connection:Terminal
Settings
Range of the magnetic adjustment:3500 / 4410 / 5600 /
6300 / 6300 / 6300 /
6300 / 6300 A
Magnetic protection nob setting xIN:2,5 / 5 / 8
Setting type In or Ith:IrTh
Equipment
Motor drive optional:yes
Use cases
Category of use:A
Standards
Standard text:IEC 60947-2
European directive WEEE:concerned
Safety
Protection index IP:IP4X
Use conditions
Operating temperature:-25…70 °C
Altitude:2000 m
Air humidity protection:for all climates
Storage/transport temperature:-35…70 °C

*All data is subject to errors and technical modifications. All prices are recommended retail prices.