Moulded Case Circuit Breaker h3 x160 TM ADJ 3P3D 80A 40kA CTC HNA080U

EAN
3250613130558
Packaging
1 Piece

Technical properties

Architecture
  • Neutral position
    without neutral
  • Number of protected poles
    3
  • Number of poles
    3 P
Functions
  • Trip Unit
    TM A/F
  • Integrated earth fault protection
    No
  • Concurrently switching N-neutral
    No
Controls and indicators
  • Motor drive integrated
    No
Main electrical features
  • Rated operational voltage Ue
    220 / 415 V
  • Frequency
    50/60 Hz
Voltage
  • Rated insulation voltage
    690 V
  • Rated impulse withstand voltage
    8 kV
  • With under voltage release
    No
Electric current
  • Rated current
    80 A
  • Thermal protection nob setting xIN
    0.63 / 0.8 / 1
  • Rating current 10°C according to IEC 60947
    93.2 A
  • Rating current 15°C according to IEC 60947
    91.6 A
  • Rating current 20°C according to IEC 60947
    90.1 A
  • Rating current 25°C according to IEC 60947
    88.5 A
  • Rating current 30°C according to IEC 60947
    86.8 A
  • Rating current 35°C according to IEC 60947
    85.2 A
  • Rating current 40°C according to IEC 60947
    83.5 A
  • Rating current 45°C according to IEC 60947
    81.7 A
  • Rating current 50°C according to IEC 60947
    80 A
  • Rating current 55°C according to IEC 60947
    78.1 A
  • Rating current 60°C according to IEC 60947
    76.3 A
  • Rating current 65°C according to IEC 60947
    74.4 A
  • Rating current 70°C according to IEC 60947
    72.4 A
  • Rated ultimate short-circuit breaking capacity Icu under 230V AC IEC 60947-2
    85 kA
  • Rated ultimate short-circuit breaking capacity Icu under 240V AC IEC 60947-2
    85 kA
  • Rated ultimate short-circuit breaking capacity Icu under 400V AC IEC 60947-2
    40 kA
  • Rated ultimate short-circuit breaking capacity Icu under 415V AC IEC 60947-2
    40 kA
  • Range of the thermal adjustment
    50 / 63 / 80 A
  • Rated ultimate short-circuit breaking capacity Icu under 380V AC IEC 60947-2
    40 kA
Dimensions
  • Depth of installed product
    68 mm
  • Height of installed product
    130 mm
  • Width of installed product
    75 mm
Frequency
  • Frequency
    50 to 60 Hz
Power
  • Power loss per pole at 0.63*In
    4.2 W
  • Power loss per pole at 0.8*In
    6.6 W
  • Total power loss at 0.63*In
    12.5 W
  • Total power loss at 0.8*In
    19.9 W
  • Total power loss under IN
    32.1 W
  • Power loss per pole at In
    10.7 W
Endurance
  • Electric endurance in number of cycles
    1000
  • Number of mechanical operations
    4000
Connection
  • Type of connection
    with screw
Settings
  • Range of the magnetic adjustment
    1000 A
Equipment
  • Number of auxiliary contacts as normally closed contact
    0
  • Number of auxiliary contacts as normally open contact
    0
  • Number of auxiliary contacts as change-over contact
    0
  • Can be accessorized
    Yes
Standards
  • European directive WEEE
    concerned
Safety
  • Protection index IP
    IP4X
Use conditions
  • Degree of pollution according to IEC 60664 / IEC 60947-2
    3
  • Altitude
    2000 m
temperatur
  • Temperature of calibration
    50 °C

Downloads

  • Product image

    Image HNA080U  | Hager Australia

    Product Image HNA080U

  • ProductNotice

    Image Instruction manuals for HNA080U  | Hager Australia

    Instruction manuals for HNA080U

    PDF
    8 MB
  • ProductECDeclaration

    Image Declaration  | Hager Australia

    Declaration

    PDF
    215 KB
  • ProductROHS

    Image RoHS certificate for HNA080U  | Hager Australia

    RoHS certificate for HNA080U

    PDF
    32 KB
    Image RoHS certificate for HNA080U  | Hager Australia

    RoHS certificate for HNA080U

    PDF
    33 KB
More documentation