Cat. Ref.:HNA126U
EAN No.:3250613131197
ex. GST*:1.367,73 $ / pc.
inc. GST*:1.504,50 $ / pc.

Technical Properties

Architecture
Type of order:Toggle
Number of poles:4 P
Type of pole:4P4D
Functions
Complete device with protection unit:yes
Trip Unit:TM A/F
Integrated earth fault protection:no
Compatibility
Compatible with DIN rail mounting:no
Main electrical features
Frequency:50/60 Hz
Rated operational voltage Ue:220/415 V
Voltage
Rated insulation voltage:690 V
Rated impulse withstand voltage:8000 V
With under voltage release:no
Electric current
Rated ultimate short-circuit breaking capacity Icu under 400V AC IEC 60947-2:40 kA
Breaking capacity on 1 pole with 400 V NF 60947-2:9 kA
Rated ultimate short-circuit breaking capacity Icu under 230V AC IEC 60947-2:85 kA
Rated ultimate short-circuit breaking capacity Icu under 240V AC IEC 60947-2:85 kA
Rated ultimate short-circuit breaking capacity Icu under 415V AC IEC 60947-2:40 kA
Thermal protection nob setting xIN:0,63/0,8/1
Current correction factors
Correction factor of rating current for 2 devices placed side-by-side:1
Correction factor of rating current for 3 devices placed side-by-side:1
Correction factor of rating current for 4 and 5 devices placed side-by-side:1
Correction factor of rating current for 6 devices placed side-by-side:1
Power
Power loss per pole at In:11 W
Total power loss under IN:33 W
Tripping
Tripmode:TM
Time of response when opening:10 ms
Endurance
Electric endurance in number of cycles:1000
Number of mechanical operations:4000
Installation, mounting
Tightening torque:6Nm
DIN rail mounting with optional adaptator:yes
Connection
Connection cross-sect. rigid cable:4 / 95mm²
Connection cross-sect. flexible conductor:4 / 70mm²
Connection:Front connection
Type of connection:with screw
Settings
Range of the magnetic adjustment:1500 A
Equipment
Motor drive optional:no
Use cases
Category of use:A
Standards
Standard text:IEC 60947-2
Safety
Protection index IP:IP4X
Use conditions
Altitude:2000 m
Air humidity protection:for all climates