Cat. Ref.:HNB201U
EAN No.:3250613347710
ex. GST*:2.622,29 $ / pc.
inc. GST*:2.884,52 $ / pc.

Technical Properties

Architecture
Type of order:Toggle
Number of poles:4 P
Type of pole:4P4D N:0;100%
Functions
Complete device with protection unit:yes
Trip Unit:TM A/A
Integrated earth fault protection:no
Compatibility
Compatible with DIN rail mounting:no
Main electrical features
Frequency:50/60 Hz
Rated operational voltage Ue:220/415 V
Voltage
Rated insulation voltage:800 V
Rated impulse withstand voltage:8000 V
With under voltage release:no
Electric current
Rated ultimate short-circuit breaking capacity Icu under 400V AC IEC 60947-2:40 kA
Rated service breaking capacity Ics AC according IEC 60947-2:50 %
Breaking capacity on 1 pole for IT 230V NF 60947-2:51 kA
Breaking capacity on 1 pole for IT 400V NF 60947-2:9 kA
Rated ultimate short-circuit breaking capacity Icu under 230V AC IEC 60947-2:85 kA
Rated ultimate short-circuit breaking capacity Icu under 240V AC IEC 60947-2:85 kA
Rated ultimate short-circuit breaking capacity Icu under 415V AC IEC 60947-2:40 kA
Rated ultimate short-circuit breaking capacity Icu under 440V AC IEC 60947-2:30 kA
Rated ultimate short-circuit breaking capacity Icu under 690V AC IEC 60947-2:4 kA
Thermal protection nob setting xIN:0,63/0,8/1
Thermal setting current on neutral pole:1 In
Current correction factors
Correction factor of rating current for 2 devices placed side-by-side:1
Correction factor of rating current for 3 devices placed side-by-side:1
Correction factor of rating current for 4 and 5 devices placed side-by-side:1
Correction factor of rating current for 6 devices placed side-by-side:1
Power
Power loss per pole at In:8,3 W
Total power loss under IN:24,8 W
Tripping
Tripmode:TM
Time of response when opening:10 ms
Endurance
Electric endurance in number of cycles:1000
Number of mechanical operations:4000
Installation, mounting
Tightening torque:12Nm
DIN rail mounting with optional adaptator:yes
Connection
Connection cross-sect. rigid cable:35 / 185mm²
Connection cross-sect. flexible conductor:35 / 150mm²
Connection:Front connection
Type of connection:Terminal
Settings
Magnetic protection nob setting xIN:6/8/10/13
Setting type In or Ith:IN
Range of the magnetic adjustment:1200/1600/2000/2600 A
Equipment
Motor drive optional:yes
Use cases
Category of use:A
Standards
Standard text:IEC 60947-2
European directive WEEE:not concerned
Safety
Protection index IP:IP4X
Use conditions
Operating temperature:-25 … 70 °C
Altitude:2000 m
Air humidity protection:for all climates
Storage/transport temperature:-35 … 70 °C

*All data is subject to errors and technical modifications. All prices are recommended retail prices.