Technical Properties
Architecture
| Neutral position: | right | |
| Number of protected poles: | 1 | |
| Number of poles: | 1 P | |
| Type of pole: | 1 P | |
| Fixing mode: | DIN rail type O (symmetrical) | |
| Curve: | C |
Compatibility
| Compatible with DIN rail mounting: | yes |
Connectivity
| Bottom connection alignement for modular devices: | Aligned terminal | |
| Top connection alignement for modular devices: | Shifted terminal |
Main electrical features
| Frequency: | 50 Hz | |
| Rated short circuit breaking capacity Icn AC according IEC60898-1: | 6 kA | |
| Type of supply voltage: | AC | |
| Rated operational voltage Ue: | 240 V |
Voltage
| Rated insulation voltage: | 250 V | |
| Max operating voltage: | 253 V | |
| Dielectric strength value of power frequency: | 2 kV | |
| Rated impulse withstand voltage: | 4000 V |
Electric current
| Rated residual operating current: | 30 mA | |
| Withstand not tripping on 8-20 μs wave: | 3 kA | |
| Rated short circuit breaking capacity Icn under 240V AC according IEC 61009-1: | 6 kA | |
| Rated service breaking capacity Ics under 240V AC according IEC 61009-1: | 6 kA | |
| Breaking and opening capacity: | 4,5 kA | |
| Magnetic regulating currrent at 40° C: | 5/10 In | |
| min/maxi threshold value of the AC thermal operation: | 1,13/1,45 In |
Electric current / temperature
| Rating current -15°C: | 12,85 A | |
| Rating current -20°C: | 13,1 A | |
| Rating current 0°C: | 12,1 A | |
| Rating current 10°C: | 11,6 A | |
| Rating current -10°C: | 12,8 A | |
| Rating current 15°C: | 11,35 A | |
| Rating current 20°C: | 11,1 A | |
| Rating current 25°C: | 10,85 A | |
| Rating current -25°C: | 13,35 A | |
| Rating current 30°C: | 10 A | |
| Rating current 35°C: | 10,35 A | |
| Rating current 40°C: | 10,1 A | |
| Rating current 45°C: | 9,85 A | |
| Rating current 5°C: | 11,85 A | |
| Rating current -5°C: | 12,35 A | |
| Rating current 50°C: | 10 A | |
| Rating current 55°C: | 9,35 A | |
| Rating current 60°C: | 9,1 A | |
| Rating current 65°C: | 8,85 A | |
| Rating current 70°C: | 8,6 A |
Current correction factors
| Correction factor of magnetic tripping with 100 Hz: | 1,1 | |
| Correction factor of magnetic tripping with 200 Hz: | 1,3 | |
| Correction factor of magnetic tripping with 400 Hz: | 1,6 | |
| Correction factor of magnetic tripping with 60 Hz: | 1 | |
| Correction factor of rating current for 2 devices placed side-by-side: | 0,95 | |
| Correction factor of rating current for 3 devices placed side-by-side: | 0,95 | |
| Correction factor of rating current for 4 and 5 devices placed side-by-side: | 0,9 | |
| Correction factor of rating current for 6 devices placed side-by-side: | 0,85 |
Power
| Power loss per pole at In: | 2,56 W | |
| Total power loss under IN: | 3,02 W |
Tripping
| Protected against nuisance tripping: | no |
Endurance
| Electric endurance in number of cycles: | 16000 | |
| Number of mechanical operations: | 20000 |
Dimensions
| Depth of installed product: | 70 mm | |
| Height of installed product: | 92 mm | |
| Width of installed product: | 17,7 mm |
Installation, mounting
| Type of top connection for modular devices: | with screw | |
| Type of bottom rail clip for modular devices: | plastic | |
| Type of top rail clip for modular devices: | NA | |
| Type of Bottom Connection for modular devices: | with screw | |
| Bottom removability for modular devices: | yes | |
| Top removability for modular devices: | no | |
| Suitable for flush-mounting: | yes |
Connection
| Upstream cage clamp delivery status: | opened | |
| Downstream cage clamp delivery status: | opened | |
| Connection cross-section at output with screw, for flexible conductor: | 1/16 mm² | |
| Connection cross-section of the access with screws, with flexible conductor: | 1/10 mm² | |
| Connection cross-section at output with screw, for massive conductor: | 1/16 mm² | |
| Connection cross-section for rigid conductor, upstream terminals with screws: | 1/16 mm² | |
| Nominal tightening torque bottom terminal: | 2,8 Nm | |
| Nominal tightening torque top terminal: | 1,9 Nm |
Cable
| Length of conductors used for the heating test (m) according to product standard: | 1 m | |
| Conductor cross-section used for heating test(mm²) according to product standard: | 1,5 mm² |
Equipment
| Can be accessorized: | no | |
| Quick connect: | no | |
| Type selective: | no |
Standards
| Standard text: | IEC 61009-1, AS/NZS 61009-1 | |
| European directive WEEE: | not concerned |
Safety
| Protection index IP: | IP20 | |
| Residual current type: | A |
Use conditions
| Degree of pollution according to IEC 60664 / IEC 60947-2: | 3 | |
| Class of energy limitation I²t: | 3 | |
| Altitude: | 2000 m | |
| Storage temperature: | -25 to 80 °C |
temperatur
| Temp.-rise limits for access. parts (not touched) according to product standard: | 60 K | |
| Temperature of calibration: | 30 °C | |
| Ambient air temperature during heating test according to the product standard: | 23,4 °C | |
| Max. admissible temperature on accessible parts (intended to be touched): | 57,92 °C | |
| Max. admissible temperature on accessible parts (manual operating means): | 48,2 °C | |
| Max. admissible temperature on access. parts (not touched for normal operation): | 59,75 °C | |
| Max. admissible temperature on terminals: | 60,18 °C | |
| Temperature-rise measured on accessible parts at In (intended to be touched): | 17,92 K | |
| Temperature-rise measured on accessible parts at In (manual operating means): | 8,2 K | |
| Temperature-rise measured on access. parts at In (not touched normal operation): | 19,75 K | |
| Temperature-rise measured on terminals at In: | 20,18 K | |
| Temp.-rise limits for access. parts (toggle) according to product standard: | 25 K | |
| Temp.rise limits for access. parts (to be touched) according to product standard: | 40 K | |
| Temperature-rise limits for terminals according to the product standard: | 65 K |
Identification
| Device family: | ADC |
*All data is subject to errors and technical modifications. All prices are recommended retail prices.