This product is not sold any longer.
This page, however, remains available for information ourposes.
Please contact your wholesaler in order to find appropriate follow-up products!
Presence det. 360° monobloc KNX/DALI |
|
Technical Properties
Architecture
Bus system: | KNX |
Functions
Constant light control: | yes | |
|
Configuration
|
Controls and indicators
|
Connectivity
Bus system radio frequent: | no | |
Bus system LON: | no | |
Bus system Powernet: | no | |
|
Voltage
Operating voltage over bus: | 21…32 V DC |
Electric current
Bus current consumption (data transfer): | 12 mA |
Measurement
Detection Method: | presence |
Detection
Detection angle: | 360 ° | |
Angle of vertical detection: | 55 ° | |
Detection field Ø, on floor: | ≈ 7 m | |
Detection field Ø, at desk height: | ≈ 5 m | |
Frontal detecting distance: | 7 m | |
Side detecting distance: | 8 m |
Materials
Colour: | white | |
RAL colour: | RAL 9010 - Pure white | |
Material: | PC-ABS | |
Surface appearance: | matt |
Dimensions
Dimensions (Ø x H): | 78 x 70 mm | |
Installation opening Ø: | 60…63 mm | |
Recommended installation height: | 2,5…3,5 m | |
Installation wall thickness: | 10…28 mm |
Lighting control
Brightness measurement range: | 5 / 1000 Lux |
Installation, mounting
Maximum Mounting Height: | 4 m | |
Installation mode: | with spring clips for ceiling installation |
Connection
Conductor cross-section (flexible): | 0,5…1,5 mm² | |
Conductor cross-section (rigid): | 0,5…1,5 mm² | |
| ||
|
Settings
Supported configuration modes: | system | |
Delay time, adjustable: | 1 mn…1 h | |
|
Scope of delivery
Bus connection included: | yes |
Equipment
Number of channels: | 1 | |
Angle of horizontal detection: | 360 ° |
Safety
Halogen free: | no |
Use conditions
Operating temperature: | -10…45 °C | |
Storage/transport temperature: | -20…60 °C | |
|
Identification
Main design line: | KNX |