Cat. Ref.:HHA078Z
EAN No.:3250613136017
ex. GST*:396,62 $ / pc.
inc. GST*:436,28 $ / pc.

Technical Properties

Architecture
Neutral position:without neutral
Number of protected poles:1
Number of poles:1 P
Type of pole:1P1D
Functions
Trip Unit:TM F/F
Concurrently switching N-neutral:no
Compatibility
Compatible with DIN rail mounting:no
Controls and indicators
Motor drive integrated:no
Main electrical features
Rated operational voltage Ue:220 / 240 V
Frequency:50/60 Hz
Voltage
Rated insulation voltage:690 V
Rated impulse withstand voltage:8 kV
With under voltage release:no
Electric current
Rated current:80 A
Thermal protection nob setting xIN:1
Rating current 10°C according to IEC 60947:106,9 A
Rating current 150°C according to IEC 60947:103,9 A
Rating current 20°C according to IEC 60947:100,9 A
Rating current 25°C according to IEC 60947:97,7 A
Rating current 30°C according to IEC 60947:94,4 A
Rating current 35°C according to IEC 60947:91 A
Rating current 40°C according to IEC 60947:87,5 A
Rating current 45°C according to IEC 60947:83,8 A
Rating current 50°C according to IEC 60947:80 A
Rating current 55°C according to IEC 60947:75,9 A
Rating current 60°C according to IEC 60947:71,6 A
Rating current 65°C according to IEC 60947:67,1 A
Rating current 70°C according to IEC 60947:62,2 A
Rated service breaking capacity Ics under 220V AC according IEC 60947-2:25 kA
Rated service breaking capacity Ics under 230V AC according IEC 60947-2:25 kA
Rated service breaking capacity Ics under 240V AC according IEC 60947-2:25 kA
Rated service breaking capacity Ics under 380V AC according IEC 60947-2:20 kA
Rated service breaking capacity Ics under 400V AC according IEC 60947-2:20 kA
Rated service breaking capacity Ics under 415V AC according IEC 60947-2:20 kA
Rated ultimate short-circuit breaking capacity Icu under 230V AC IEC 60947-2:35 kA
Rated ultimate short-circuit breaking capacity Icu under 240V AC IEC 60947-2:35 kA
Rated ultimate short-circuit breaking capacity Icu under 400V AC IEC 60947-2:25 kA
Rated ultimate short-circuit breaking capacity Icu under 415V AC IEC 60947-2:25 kA
Range of the thermal adjustment:80 A
Rated ultimate short-circuit breaking capacity Icu under 380V AC IEC 60947-2:25 kA
Frequency
Frequency:50 to 60 Hz
Power
Total power loss under IN:4,8 W
Power loss per pole at In:4,8 W
Endurance
Electric endurance in number of cycles:1000
Number of mechanical operations:4000
Dimensions
Depth of installed product:68 mm
Height of installed product:130 mm
Width of installed product:25 mm
Critical distance switching emission/earthed part bottom:40 mm
Critical distance switching emission/earthed part left:50 mm
Critical distance switching emission/earthed part right:50 mm
Critical distance switching emission/earthed part top:40 mm
Critical distance switching emission/insulated plate:30 mm
Critical distance switching emission/live part:50 mm
Connection
Type of connection:with screw
Settings
Range of the magnetic adjustment:1000 A
Equipment
Can be accessorized:yes
Standards
Standard text:IEC 60947-2
European directive WEEE:concerned
Product categories described in the W3E directive 2012/19/EU:Category 5
Safety
Protection index IP:IP4X
Use conditions
Degree of pollution according to IEC 60664 / IEC 60947-2:3
Altitude:2000 m
temperatur
Temperature of calibration:50 °C

*All data is subject to errors and technical modifications. All prices are recommended retail prices.