Technical Properties
Architecture
![]() | Type of order: | Toggle |
![]() | Number of poles: | 4 P |
![]() | Type of pole: | 4P4D |
Functions
![]() | Complete device with protection unit: | yes |
![]() | Trip Unit: | TM A/F |
![]() | Integrated earth fault protection: | no |
Compatibility
![]() | Compatible with DIN rail mounting: | no |
Main electrical features
![]() | Rated operational voltage Ue: | 220 / 415 V |
![]() | Frequency: | 50/60 Hz |
Voltage
![]() | Rated insulation voltage: | 690 V |
![]() | Rated impulse withstand voltage: | 8 kV |
![]() | With under voltage release: | no |
Electric current
![]() | Rated current: | 125 A |
![]() | Thermal protection nob setting xIN: | 0,63 / 0,8 / 1 |
![]() | Breaking capacity on 1 pole for IT 400V NF 60947-2: | 9 kA |
![]() | Rated ultimate short-circuit breaking capacity Icu under 230V AC IEC 60947-2: | 85 kA |
![]() | Rated ultimate short-circuit breaking capacity Icu under 240V AC IEC 60947-2: | 85 kA |
![]() | Rated ultimate short-circuit breaking capacity Icu under 400V AC IEC 60947-2: | 40 kA |
![]() | Rated ultimate short-circuit breaking capacity Icu under 415V AC IEC 60947-2: | 40 kA |
Current correction factors
![]() | Correction factor of rating current for 2 devices placed side-by-side: | 1 |
![]() | Correction factor of rating current for 3 devices placed side-by-side: | 1 |
![]() | Correction factor of rating current for 4 and 5 devices placed side-by-side: | 1 |
![]() | Correction factor of rating current for 6 devices placed side-by-side: | 1 |
Power
![]() | Total power loss under IN: | 33 W |
![]() | Power loss per pole at In: | 11 W |
Tripping
![]() | Tripmode: | TM |
![]() | Time of response when opening: | 10 ms |
Endurance
![]() | Electric endurance in number of cycles: | 1000 |
![]() | Number of mechanical operations: | 4000 |
Installation, mounting
![]() | Tightening torque: | 6Nm |
![]() | DIN rail mounting with optional adaptator: | yes |
Connection
![]() | Connection cross-sect. flexible conductor: | 4 / 70mm² |
![]() | Connection cross-sect. rigid cable: | 4 / 95mm² |
![]() | Connection: | Front connection |
![]() | Type of connection: | with screw |
Settings
![]() | Range of the magnetic adjustment: | 1500 A |
Equipment
![]() | Motor drive optional: | no |
Use cases
![]() | Category of use: | A |
Standards
![]() | Standard text: | IEC 60947-2 |
Safety
![]() | Protection index IP: | IP4X |
Use conditions
![]() | Altitude: | 2000 m |
![]() | Air humidity protection: | for all climates |