This product is not sold any longer.
This page, however, remains available for information ourposes.
Please contact your wholesaler in order to find appropriate follow-up products!
RCBO 1M 1P 10kA C-6A 10mA A |
|
Technical Properties
Architecture
| Neutral position: | right | |
| Number of protected poles: | 1 | |
| Number of poles: | 1 P | |
| Type of pole: | 1 P | |
| Fixing mode: | Din-Rail | |
| Curve: | C |
Functions
| Concurrently switching N-neutral: | no | |
| Sealable: | yes |
Compatibility
| Compatible with DIN rail mounting: | yes |
Controls and indicators
| With fault indicator: | no |
Main electrical features
| Rated short circuit breaking capacity Icn AC according IEC60898-1: | 10 kA | |
| Rated operational voltage Ue: | 240 V | |
| Frequency: | 50 Hz |
Voltage
| Rated insulation voltage: | 250 V | |
| Max operating voltage: | 253 V | |
| Rated impulse withstand voltage: | 4000 V |
Electric current
| Rated residual operating current: | 10 mA | |
| Rated current: | 6 A | |
| Withstand not tripping on 8-20 μs wave: | 3 kA | |
| Breaking and opening capacity: | 6 kA | |
| min/maxi threshold value of the AC thermal operation: | 1,13 / 1,45 In | |
| Magnetic regulating currrent: | 5 / 10 In | |
| Rated short circuit breaking capacity Icn under 230V AC according IEC60898-1: | 10 kA |
Electric current / temperature
| Rating current -25°C: | 7,72 A | |
| Rating current -20°C: | 7,58 A | |
| Rating current -15°C: | 7,43 A | |
| Rating current -10°C: | 7,29 A | |
| Rating current -5°C: | 7,14 A | |
| Rating current 0°C: | 6,99 A | |
| Rating current 5°C: | 6,83 A | |
| Rating current 10°C: | 6,67 A | |
| Rating current 15°C: | 6,51 A | |
| Rating current 20°C: | 6,35 A | |
| Rating current 25°C: | 6,18 A | |
| Rating current 30°C: | 6 A | |
| Rating current 35°C: | 5,82 A | |
| Rating current 40°C: | 5,63 A | |
| Rating current 45°C: | 5,44 A | |
| Rating current 50°C: | 5,24 A | |
| Rating current 55°C: | 5,03 A | |
| Rating current 60°C: | 4,81 A |
Current correction factors
| Correction factor of rating current for 2 devices placed side-by-side: | 1 | |
| Correction factor of rating current for 3 devices placed side-by-side: | 0,95 | |
| Correction factor of rating current for 4 and 5 devices placed side-by-side: | 0,9 | |
| Correction factor of rating current for 6 devices placed side-by-side: | 0,85 |
Frequency
| Frequency: | 50 Hz |
Power
| Total power loss under IN: | 1,5 W | |
| Power loss per pole at In: | 1,24 W |
Tripping
| Protected against nuisance tripping: | no |
Endurance
| Electric endurance in number of cycles: | 2000 | |
| Number of mechanical operations: | 1000 |
Dimensions
| Depth of installed product: | 70 mm | |
| Height of installed product: | 110 mm | |
| Width of installed product: | 17,8 mm |
Installation, mounting
| Tightening torque: | 2,1Nm | |
| Type of top rail clip for modular devices: | NA | |
| Type of bottom rail clip for modular devices: | metallic isolated | |
| Top removability for modular devices: | no | |
| Bottom removability for modular devices: | no | |
| 360° product mounting position: | yes |
Connection
| Connection cross-section at output with screw, for flexible conductor: | 1 / 16 mm² | |
| Connection cross-section at output with screw, for massive conductor: | 1 / 25 mm² | |
| Connection cross-section for rigid conductor, upstream terminals with screws: | 1 / 25 mm² | |
| Connection cross-section of the access with screws, with flexible conductor: | 1 / 16 mm² |
Equipment
| With transparent product label holder: | no |
Standards
| Standard text: | IEC 61009-1, AS/NZS 61009-1 | |
| European directive WEEE: | concerned |
Safety
| Protection index IP: | IP20 | |
| Residual current type: | A |
Use conditions
| Degree of pollution according to IEC 60664 / IEC 60947-2: | 2 | |
| Class of energy limitation I²t: | 3 | |
| Altitude: | 2000 m | |
| Air humidity protection: | Execution II |