This product is not sold any longer.
This page, however, remains available for information ourposes.
Please contact your wholesaler in order to find appropriate follow-up products!
![]() | RCBO 1M 1P 6kA C-13A 30mA A |
| ![]() |
Technical Properties
Architecture
![]() | Neutral position: | right |
![]() | Number of protected poles: | 1 |
![]() | Number of poles: | 1 P |
![]() | Type of pole: | 1 P |
![]() | Curve: | C |
Connectivity
![]() | Top connection alignement for modular devices: | Shifted terminal |
Main electrical features
![]() | Rated short circuit breaking capacity Icn AC according IEC60898-1: | 6 kA |
![]() | Rated operational voltage Ue: | 240 V |
![]() | Frequency: | 50 Hz |
Voltage
![]() | Rated insulation voltage: | 250 V |
![]() | Max operating voltage: | 253 V |
![]() | Rated impulse withstand voltage: | 4000 V |
Electric current
![]() | Rated residual operating current: | 30 mA |
![]() | Rated current: | 13 A |
![]() | Breaking and opening capacity: | 4,5 kA |
![]() | min/maxi threshold value of the AC thermal operation: | 1,13 / 1,45 In |
![]() | Magnetic regulating currrent: | 5 / 10 In |
![]() | Rated short circuit breaking capacity Icn under 230V AC according IEC60898-1: | 6 kA |
Electric current / temperature
![]() | Rating current -25°C: | 16,1 A |
![]() | Rating current -20°C: | 15,8 A |
![]() | Rating current -15°C: | 15,6 A |
![]() | Rating current -10°C: | 15,3 A |
![]() | Rating current -5°C: | 15 A |
![]() | Rating current 0°C: | 14,8 A |
![]() | Rating current 5°C: | 14,5 A |
![]() | Rating current 10°C: | 14,2 A |
![]() | Rating current 15°C: | 13,9 A |
![]() | Rating current 20°C: | 13,6 A |
![]() | Rating current 25°C: | 13,3 A |
![]() | Rating current 30°C: | 13 A |
![]() | Rating current 35°C: | 12,8 A |
![]() | Rating current 40°C: | 12,5 A |
![]() | Rating current 45°C: | 12,3 A |
![]() | Rating current 50°C: | 12 A |
![]() | Rating current 55°C: | 11,8 A |
![]() | Rating current 60°C: | 11,5 A |
Current correction factors
![]() | Correction factor of rating current for 2 devices placed side-by-side: | 0,95 |
![]() | Correction factor of rating current for 3 devices placed side-by-side: | 0,95 |
![]() | Correction factor of rating current for 4 and 5 devices placed side-by-side: | 0,9 |
![]() | Correction factor of rating current for 6 devices placed side-by-side: | 0,85 |
![]() | Correction factor of magnetic tripping with 100 Hz: | 1,1 |
![]() | Correction factor of magnetic tripping with 200 Hz: | 1,3 |
![]() | Correction factor of magnetic tripping with 400 Hz: | 1,6 |
![]() | Correction factor of magnetic tripping with 60 Hz: | 1 |
Frequency
![]() | Frequency: | 50 Hz |
Power
![]() | Total power loss under IN: | 5,1 W |
Endurance
![]() | Electric endurance in number of cycles: | 2000 |
![]() | Number of mechanical operations: | 2000 |
Dimensions
![]() | Depth of installed product: | 70 mm |
![]() | Height of installed product: | 92 mm |
![]() | Width of installed product: | 17,7 mm |
Installation, mounting
![]() | Tightening torque: | 2.3Nm |
Connection
![]() | Connection cross-sect. flexible conductor: | 1 / 10mm² |
![]() | Connection cross-sect. rigid cable: | 1 / 16mm² |
Cable
![]() | Length of conductors used for the heating test (m) according to product standard: | 1 m |
![]() | Conductor cross-section used for heating test(mm²) according to product standard: | 1,5 mm² |
Equipment
![]() | Can be accessorized: | no |
Standards
![]() | Standard text: | IEC 61009-1, AS/NZS 61009-1 |
![]() | European directive WEEE: | not concerned |
Safety
![]() | Protection index IP: | IP20 |
![]() | Residual current type: | A |
Use conditions
![]() | Operating temperature: | -5…55 °C |
![]() | Degree of pollution according to IEC 60664 / IEC 60947-2: | 3 |
![]() | Class of energy limitation I²t: | 3 |
![]() | Altitude: | 2000 m |
![]() | Air humidity protection: | Execution II |
![]() | Storage/transport temperature: | -25…80 °C |
temperatur
![]() | Temperature of calibration: | 30 °C |
![]() | Ambient air temperature during heating test according to the product standard: | 22,7 °C |
![]() | Max. admissible temperature on accessible parts (intended to be touched): | 36,6 °C |
![]() | Max. admissible temperature on accessible parts (manual operating means): | 27,8 °C |
![]() | Max. admissible temperature on access. parts (not touched for normal operation): | 51 °C |
![]() | Max. admissible temperature on terminals: | 44 °C |
![]() | Temp.-rise limits for access. parts (toggle) according to product standard: | 25 K |
![]() | Temp.-rise limits for access. parts (not touched) according to product standard: | 60 K |
![]() | Temp.rise limits for access. parts (to be touched) according to product standard: | 40 K |
![]() | Temperature-rise limits for terminals according to the product standard: | 65 K |
![]() | Temperature-rise measured on accessible parts at In (manual operating means): | 5,1 K |
![]() | Temperature-rise measured on access. parts at In (not touched normal operation): | 28,3 K |
![]() | Temperature-rise measured on accessible parts at In (intended to be touched): | 13,9 K |
![]() | Temperature-rise measured on terminals at In: | 21,3 K |