This product is not sold any longer.
This page, however, remains available for information ourposes.
Please contact your wholesaler in order to find appropriate follow-up products!
RCBO 1M 1P 6kA C-16A 30mA A |
|
Technical Properties
Architecture
Neutral position: | right | |
Number of protected poles: | 1 | |
Number of poles: | 1 P | |
Type of pole: | 1 P | |
Curve: | C |
Connectivity
Top connection alignement for modular devices: | Shifted terminal |
Main electrical features
Rated short circuit breaking capacity Icn AC according IEC60898-1: | 6 kA | |
Rated operational voltage Ue: | 240 V | |
Frequency: | 50 Hz |
Voltage
Rated insulation voltage: | 250 V | |
Max operating voltage: | 253 V | |
Rated impulse withstand voltage: | 4000 V |
Electric current
Rated residual operating current: | 30 mA | |
Rated current: | 16 A | |
Breaking and opening capacity: | 4,5 kA | |
min/maxi threshold value of the AC thermal operation: | 1,13 / 1,45 In | |
Magnetic regulating currrent: | 5 / 10 In | |
Rated short circuit breaking capacity Icn under 230V AC according IEC60898-1: | 6 kA |
Electric current / temperature
Rating current -25°C: | 20,2 A | |
Rating current -20°C: | 19,8 A | |
Rating current -15°C: | 19,5 A | |
Rating current -10°C: | 19,1 A | |
Rating current -5°C: | 18,8 A | |
Rating current 0°C: | 18,4 A | |
Rating current 5°C: | 18 A | |
Rating current 10°C: | 17,6 A | |
Rating current 15°C: | 17,2 A | |
Rating current 20°C: | 16,8 A | |
Rating current 25°C: | 16,4 A | |
Rating current 30°C: | 16 A | |
Rating current 35°C: | 15,7 A | |
Rating current 40°C: | 15,4 A | |
Rating current 45°C: | 15,1 A | |
Rating current 50°C: | 14,8 A | |
Rating current 55°C: | 14,5 A | |
Rating current 60°C: | 14,2 A |
Current correction factors
Correction factor of rating current for 2 devices placed side-by-side: | 0,95 | |
Correction factor of rating current for 3 devices placed side-by-side: | 0,95 | |
Correction factor of rating current for 4 and 5 devices placed side-by-side: | 0,9 | |
Correction factor of rating current for 6 devices placed side-by-side: | 0,85 | |
Correction factor of magnetic tripping with 100 Hz: | 1,1 | |
Correction factor of magnetic tripping with 200 Hz: | 1,3 | |
Correction factor of magnetic tripping with 400 Hz: | 1,6 | |
Correction factor of magnetic tripping with 60 Hz: | 1 |
Frequency
Frequency: | 50 Hz |
Power
Total power loss under IN: | 6,5 W |
Endurance
Electric endurance in number of cycles: | 2000 | |
Number of mechanical operations: | 1000 |
Dimensions
Depth of installed product: | 70 mm | |
Height of installed product: | 92 mm | |
Width of installed product: | 17,7 mm |
Installation, mounting
Tightening torque: | 2.3Nm |
Connection
Connection cross-sect. flexible conductor: | 1 / 10mm² | |
Connection cross-sect. rigid cable: | 1 / 16mm² |
Cable
Length of conductors used for the heating test (m) according to product standard: | 1 m | |
Conductor cross-section used for heating test(mm²) according to product standard: | 2,5 mm² |
Equipment
Can be accessorized: | no |
Standards
Standard text: | IEC 61009-1, AS/NZS 61009-1 | |
European directive WEEE: | not concerned |
Safety
Protection index IP: | IP20 | |
Residual current type: | A |
Use conditions
Operating temperature: | -5…55 °C | |
Degree of pollution according to IEC 60664 / IEC 60947-2: | 3 | |
Class of energy limitation I²t: | 3 | |
Altitude: | 2000 m | |
Air humidity protection: | Execution II | |
Storage/transport temperature: | -25…80 °C |
temperatur
Temperature of calibration: | 30 °C | |
Ambient air temperature during heating test according to the product standard: | 23,2 °C | |
Max. admissible temperature on accessible parts (intended to be touched): | 37,5 °C | |
Max. admissible temperature on accessible parts (manual operating means): | 28,9 °C | |
Max. admissible temperature on access. parts (not touched for normal operation): | 47,5 °C | |
Max. admissible temperature on terminals: | 40,8 °C | |
Temp.-rise limits for access. parts (toggle) according to product standard: | 25 K | |
Temp.-rise limits for access. parts (not touched) according to product standard: | 60 K | |
Temp.rise limits for access. parts (to be touched) according to product standard: | 40 K | |
Temperature-rise limits for terminals according to the product standard: | 65 K | |
Temperature-rise measured on accessible parts at In (manual operating means): | 6,2 K | |
Temperature-rise measured on access. parts at In (not touched normal operation): | 24,8 K | |
Temperature-rise measured on accessible parts at In (intended to be touched): | 14,8 K | |
Temperature-rise measured on terminals at In: | 18,1 K |