This product is not sold any longer.
This page, however, remains available for information ourposes.
Please contact your wholesaler in order to find appropriate follow-up products!
RCBO 1M 1P 6kA C-20A 30mA A |
|
Technical Properties
Architecture
| Neutral position: | right | |
| Number of protected poles: | 1 | |
| Number of poles: | 1 P | |
| Type of pole: | 1 P | |
| Curve: | C |
Connectivity
| Top connection alignement for modular devices: | Shifted terminal |
Main electrical features
| Rated short circuit breaking capacity Icn AC according IEC60898-1: | 6 kA | |
| Rated operational voltage Ue: | 240 V | |
| Frequency: | 50 Hz |
Voltage
| Rated insulation voltage: | 250 V | |
| Max operating voltage: | 253 V | |
| Rated impulse withstand voltage: | 4000 V |
Electric current
| Rated residual operating current: | 30 mA | |
| Rated current: | 20 A | |
| Breaking and opening capacity: | 4,5 kA | |
| min/maxi threshold value of the AC thermal operation: | 1,13 / 1,45 In | |
| Magnetic regulating currrent: | 5 / 10 In | |
| Rated short circuit breaking capacity Icn under 230V AC according IEC60898-1: | 6 kA |
Electric current / temperature
| Rating current -25°C: | 24,6 A | |
| Rating current -20°C: | 24,2 A | |
| Rating current -15°C: | 23,8 A | |
| Rating current -10°C: | 23,4 A | |
| Rating current -5°C: | 23 A | |
| Rating current 0°C: | 22,6 A | |
| Rating current 5°C: | 22,2 A | |
| Rating current 10°C: | 21,8 A | |
| Rating current 15°C: | 21,4 A | |
| Rating current 20°C: | 20,9 A | |
| Rating current 25°C: | 20,5 A | |
| Rating current 30°C: | 20 A | |
| Rating current 35°C: | 19,7 A | |
| Rating current 40°C: | 19,4 A | |
| Rating current 45°C: | 19 A | |
| Rating current 50°C: | 18,7 A | |
| Rating current 55°C: | 18,4 A | |
| Rating current 60°C: | 18 A |
Current correction factors
| Correction factor of rating current for 2 devices placed side-by-side: | 0,95 | |
| Correction factor of rating current for 3 devices placed side-by-side: | 0,95 | |
| Correction factor of rating current for 4 and 5 devices placed side-by-side: | 0,9 | |
| Correction factor of rating current for 6 devices placed side-by-side: | 0,85 | |
| Correction factor of magnetic tripping with 100 Hz: | 1,1 | |
| Correction factor of magnetic tripping with 200 Hz: | 1,2 | |
| Correction factor of magnetic tripping with 400 Hz: | 1,6 | |
| Correction factor of magnetic tripping with 60 Hz: | 1 |
Frequency
| Frequency: | 50 Hz |
Power
| Total power loss under IN: | 9,8 W |
Endurance
| Electric endurance in number of cycles: | 2000 | |
| Number of mechanical operations: | 2000 |
Dimensions
| Depth of installed product: | 70 mm | |
| Height of installed product: | 92 mm | |
| Width of installed product: | 17,7 mm |
Installation, mounting
| Tightening torque: | 2.3Nm |
Connection
| Connection cross-sect. flexible conductor: | 1 / 10mm² | |
| Connection cross-sect. rigid cable: | 1 / 16mm² |
Cable
| Length of conductors used for the heating test (m) according to product standard: | 1 m | |
| Conductor cross-section used for heating test(mm²) according to product standard: | 2,5 mm² |
Equipment
| Can be accessorized: | no |
Standards
| Standard text: | IEC 61009-1, AS/NZS 61009-1 | |
| European directive WEEE: | not concerned |
Safety
| Protection index IP: | IP20 | |
| Residual current type: | A |
Use conditions
| Operating temperature: | -5…55 °C | |
| Degree of pollution according to IEC 60664 / IEC 60947-2: | 3 | |
| Class of energy limitation I²t: | 3 | |
| Altitude: | 2000 m | |
| Air humidity protection: | Execution II | |
| Storage/transport temperature: | -25…80 °C |
temperatur
| Temperature of calibration: | 30 °C | |
| Ambient air temperature during heating test according to the product standard: | 23,2 °C | |
| Max. admissible temperature on accessible parts (intended to be touched): | 43,4 °C | |
| Max. admissible temperature on accessible parts (manual operating means): | 31 °C | |
| Max. admissible temperature on access. parts (not touched for normal operation): | 58,1 °C | |
| Max. admissible temperature on terminals: | 59,8 °C | |
| Temp.-rise limits for access. parts (toggle) according to product standard: | 25 K | |
| Temp.-rise limits for access. parts (not touched) according to product standard: | 60 K | |
| Temp.rise limits for access. parts (to be touched) according to product standard: | 40 K | |
| Temperature-rise limits for terminals according to the product standard: | 65 K | |
| Temperature-rise measured on accessible parts at In (manual operating means): | 8,3 K | |
| Temperature-rise measured on access. parts at In (not touched normal operation): | 35,4 K | |
| Temperature-rise measured on accessible parts at In (intended to be touched): | 20,7 K | |
| Temperature-rise measured on terminals at In: | 37,1 K |