RCBO 1M 1P 6kA C-25A 30mA A

Cat. Ref.:ADC325T
EAN No.:3250611069546
This product is not sold any longer.
This page, however, remains available for information ourposes.
Please contact your wholesaler in order to find appropriate follow-up products!

Technical Properties

Architecture
Neutral position:right
Number of protected poles:1
Number of poles:1 P
Type of pole:1 P
Curve:C
Connectivity
Top connection alignement for modular devices:Shifted terminal
Main electrical features
Rated short circuit breaking capacity Icn AC according IEC60898-1:6 kA
Rated operational voltage Ue:240 V
Frequency:50 Hz
Voltage
Rated insulation voltage:250 V
Max operating voltage:253 V
Rated impulse withstand voltage:4000 V
Electric current
Rated residual operating current:30 mA
Rated current:25 A
Breaking and opening capacity:4,5 kA
min/maxi threshold value of the AC thermal operation:1,13 / 1,45 In
Magnetic regulating currrent:5 / 10 In
Rated short circuit breaking capacity Icn under 230V AC according IEC60898-1:6 kA
Electric current / temperature
Rating current -25°C:36 A
Rating current -20°C:35 A
Rating current -15°C:34 A
Rating current -10°C:33 A
Rating current -5°C:32 A
Rating current 0°C:31 A
Rating current 5°C:30 A
Rating current 10°C:29 A
Rating current 15°C:28 A
Rating current 20°C:27 A
Rating current 25°C:26 A
Rating current 30°C:25 A
Rating current 35°C:24,7 A
Rating current 40°C:24,3 A
Rating current 45°C:23,9 A
Rating current 50°C:23,6 A
Rating current 55°C:23,2 A
Rating current 60°C:22,8 A
Current correction factors
Correction factor of rating current for 2 devices placed side-by-side:0,95
Correction factor of rating current for 3 devices placed side-by-side:0,95
Correction factor of rating current for 4 and 5 devices placed side-by-side:0,9
Correction factor of rating current for 6 devices placed side-by-side:0,85
Correction factor of magnetic tripping with 100 Hz:1,1
Correction factor of magnetic tripping with 200 Hz:1,3
Correction factor of magnetic tripping with 400 Hz:1,6
Correction factor of magnetic tripping with 60 Hz:1
Frequency
Frequency:50 Hz
Power
Total power loss under IN:10,1 W
Endurance
Electric endurance in number of cycles:2000
Number of mechanical operations:2000
Dimensions
Depth of installed product:70 mm
Height of installed product:92 mm
Width of installed product:17,7 mm
Installation, mounting
Tightening torque:2.3Nm
Connection
Connection cross-sect. flexible conductor:1 / 10mm²
Connection cross-sect. rigid cable:1 / 16mm²
Cable
Length of conductors used for the heating test (m) according to product standard:1 m
Conductor cross-section used for heating test(mm²) according to product standard:4 mm²
Equipment
Can be accessorized:no
Standards
Standard text:IEC 61009-1, AS/NZS
61009-1
European directive WEEE:not concerned
Safety
Protection index IP:IP20
Residual current type:A
Use conditions
Operating temperature:-5…55 °C
Degree of pollution according to IEC 60664 / IEC 60947-2:3
Class of energy limitation I²t:3
Altitude:2000 m
Air humidity protection:Execution II
Storage/transport temperature:-25…80 °C
temperatur
Temperature of calibration:30 °C
Ambient air temperature during heating test according to the product standard:23,2 °C
Max. admissible temperature on accessible parts (intended to be touched):42,9 °C
Max. admissible temperature on accessible parts (manual operating means):32 °C
Max. admissible temperature on access. parts (not touched for normal operation):51,2 °C
Max. admissible temperature on terminals:54,8 °C
Temp.-rise limits for access. parts (toggle) according to product standard:25 K
Temp.-rise limits for access. parts (not touched) according to product standard:60 K
Temp.rise limits for access. parts (to be touched) according to product standard:40 K
Temperature-rise limits for terminals according to the product standard:65 K
Temperature-rise measured on accessible parts at In (manual operating means):9,3 K
Temperature-rise measured on access. parts at In (not touched normal operation):28,5 K
Temperature-rise measured on accessible parts at In (intended to be touched):20,2 K
Temperature-rise measured on terminals at In:32,1 K