RCCB 4P 100A 30mA A

Cat. Ref.:CD485T
EAN No.:3250611644989
This product is not sold any longer.
This page, however, remains available for information ourposes.
Please contact your wholesaler in order to find appropriate follow-up products!

Technical Properties

Architecture
Neutral position:right
Number of poles:4 P
Fixing mode:DIN rail type O
(symmetrical)
Functions
Sealable:yes
Controls and indicators
With fault indicator:yes
Main electrical features
Frequency:50 Hz
Electric current
Rated residual operating current:30 mA
Rated current:100 A
Withstand not tripping on 8-20 μs wave:0,25 kA
Breaking and opening capacity:1,5 kA
Rated conditional short-circuit current Inc according to EN 61008-1:6 kA
Electric current / temperature
Rating current -25°C:100 A
Rating current -20°C:100 A
Rating current -15°C:100 A
Rating current -10°C:100 A
Rating current -5°C:100 A
Rating current 0°C:100 A
Rating current 5°C:100 A
Rating current 10°C:100 A
Rating current 15°C:100 A
Rating current 20°C:100 A
Rating current 25°C:100 A
Rating current 30°C:100 A
Rating current 35°C:100 A
Rating current 40°C:100 A
Rating current 45°C:99 A
Rating current 50°C:94 A
Rating current 55°C:90 A
Rating current 60°C:83 A
Rating current 65°C:72 A
Rating current 70°C:59 A
Frequency
Frequency:50 Hz
Power
Total power loss under IN:30,2 W
Power loss per pole at In:11,9 W
Tripping
Protected against nuisance tripping:no
Short-time delayed tripping:no
Endurance
Electric endurance in number of cycles:2000
Number of mechanical operations:4000
Dimensions
Depth of installed product:70 mm
Height of installed product:86 mm
Width of installed product:70 mm
Construction size (DIN 43880):1
Installation, mounting
Type of top rail clip for modular devices:NA
Type of bottom rail clip for modular devices:metallic
Top removability for modular devices:no
Bottom removability for modular devices:no
360° product mounting position:yes
Connection
Type of connection:with screw
Equipment
With interlocking device:yes
Standards
Standard text:IEC 61008-1, AS/NZS
61008-1
European directive WEEE:not concerned
Safety
Protection index IP:IP20
Residual current type:A
Use conditions
Operating temperature:-25…40 °C
Degree of pollution according to IEC 60664 / IEC 60947-2:2
Altitude:2000 m
Storage/transport temperature:-55…70 °C