This product is not sold any longer.
This page, however, remains available for information ourposes.
Please contact your wholesaler in order to find appropriate follow-up products!
RCCB 2P 80A 100mA A |
|
Technical Properties
Architecture
Neutral position: | right | |
Number of poles: | 2 P | |
Fixing mode: | DIN rail type O (symmetrical) |
Functions
Sealable: | yes |
Controls and indicators
With fault indicator: | yes |
Main electrical features
Frequency: | 50 Hz |
Electric current
Rated residual operating current: | 100 mA | |
Rated current: | 80 A | |
Withstand not tripping on 8-20 μs wave: | 0,25 kA | |
Breaking and opening capacity: | 1,5 kA | |
Rated conditional short-circuit current Inc according to EN 61008-1: | 6 kA |
Electric current / temperature
Rating current -25°C: | 80 A | |
Rating current -20°C: | 80 A | |
Rating current -15°C: | 80 A | |
Rating current -10°C: | 80 A | |
Rating current -5°C: | 80 A | |
Rating current 0°C: | 80 A | |
Rating current 5°C: | 80 A | |
Rating current 10°C: | 80 A | |
Rating current 15°C: | 80 A | |
Rating current 20°C: | 80 A | |
Rating current 25°C: | 80 A | |
Rating current 30°C: | 80 A | |
Rating current 35°C: | 80 A | |
Rating current 40°C: | 80 A | |
Rating current 45°C: | 80 A | |
Rating current 50°C: | 80 A | |
Rating current 55°C: | 80 A | |
Rating current 60°C: | 74 A | |
Rating current 65°C: | 66 A | |
Rating current 70°C: | 56 A |
Frequency
Frequency: | 50 Hz |
Power
Total power loss under IN: | 8,4 W | |
Power loss per pole at In: | 4,2 W |
Tripping
Protected against nuisance tripping: | no | |
Short-time delayed tripping: | no |
Endurance
Electric endurance in number of cycles: | 2000 | |
Number of mechanical operations: | 4000 |
Dimensions
Depth of installed product: | 70 mm | |
Height of installed product: | 83 mm | |
Width of installed product: | 35 mm | |
Construction size (DIN 43880): | 1 |
Installation, mounting
Type of top rail clip for modular devices: | NA | |
Type of bottom rail clip for modular devices: | metallic | |
Top removability for modular devices: | no | |
Bottom removability for modular devices: | no | |
360° product mounting position: | yes |
Connection
Type of connection: | with screw |
Equipment
With interlocking device: | yes |
Standards
Standard text: | IEC 61008-1, AS/NZS 61008-1 | |
European directive WEEE: | not concerned |
Safety
Protection index IP: | IP20 | |
Residual current type: | A |
Use conditions
Operating temperature: | -25…40 °C | |
Degree of pollution according to IEC 60664 / IEC 60947-2: | 2 | |
Altitude: | 2000 m | |
Storage/transport temperature: | -55…70 °C |