This product is not sold any longer.
This page, however, remains available for information ourposes.
Please contact your wholesaler in order to find appropriate follow-up products!
![]() | EIB Presence detector |
| ![]() |
Technical Properties
Architecture
![]() | Bus system: | KNX |
Functions
![]() |
|
Configuration
![]() |
| |
![]() |
|
Connectivity
![]() | Bus system radio frequent: | no |
![]() | Bus system LON: | no |
![]() | Bus system Powernet: | no |
Voltage
![]() | Operating voltage over bus: | 21…32 V DC |
Electric current
![]() | Bus current consumption (data transfer): | 12 mA |
![]() | Bus current consumption (idle): | 12 mA |
Measurement
![]() | Detection Method: | presence |
Detection
![]() | Detection angle: | 360 ° |
![]() | Angle of vertical detection: | 55 ° |
![]() | Frontal detecting distance: | 7 m |
![]() | Side detecting distance: | 6 m |
Materials
![]() | Colour: | white |
![]() | RAL colour: | RAL 9010 - Pure white |
![]() | Material: | PC-ABS |
![]() | Surface appearance: | matt |
Dimensions
![]() | Dimensions (Ø x H): | 110 x 44 mm |
![]() | Recommended installation height: | 2,5…3,5 m |
Lighting control
![]() | Brightness measurement range: | 5 / 1200 Lux |
Installation, mounting
![]() | Maximum Mounting Height: | 4 m |
![]() | Installation mode: | for ceiling mounting in 60 surface-mounted or hollow-wall box |
Connection
![]() |
| |
![]() |
|
Settings
![]() | Supported configuration modes: | system, easy |
![]() | Delay ON: | 30 s |
![]() | HVAC-channel adjustable: | ≈ 30 s ... 60 mn |
![]() | Delay time, adjustable: | ≈ 1…30 mn |
![]() |
|
Scope of delivery
![]() | Bus connection included: | yes |
Accessories included
![]() |
|
Equipment
![]() | Number of channels: | 1 |
![]() | Switch on delay HVAC-channel: | 15 mn |
![]() | Angle of horizontal detection: | 360 ° |
![]() |
|
Safety
![]() | Halogen free: | no |
Use conditions
![]() | Operating temperature: | 0…45 °C |
![]() | Storage/transport temperature: | -10…60 °C |
![]() |
|
Identification
![]() | Main design line: | KNX |