![]() | OUTPUT 16 -FOLD 16A C-LOAD ADAPTED / NE |
| ![]() |
Technical Properties
Architecture
![]() | Bus system: | yes |
![]() | Fixing mode: | REG |
Functions
![]() | Operating mode: | any combined operation from drive and switching functions possible |
![]() |
| |
![]() |
| |
![]() |
| |
![]() |
| |
![]() |
|
Controls and indicators
![]() | Indicator lamp: | yes |
![]() |
| |
![]() |
| |
![]() |
| |
![]() |
|
Connectivity
![]() | Bus system radio frequent: | no |
![]() | Bus system LON: | no |
![]() | Bus system Powernet: | no |
Main electrical features
![]() | Rated operational voltage Ue: | 230 V |
![]() | Frequency: | 50/60 Hz |
![]() | Rated current: | 16 A |
Voltage
![]() | Operating voltage over bus: | 21…32 V DC |
![]() | Output voltage: | 230 V AC |
![]() | System supply voltage: | 30V DC via bus |
Electric current
![]() | Bus current consumption (data transfer): | 5 mA |
![]() | Bus current consumption (idle): | 3 mA |
![]() | Maximum through current: | 16 A |
![]() | Rated current: | 16 A |
![]() | Withstand current in AC1 for the contact path or zone 1: | 16 A |
Power
![]() | Max. power with electronic transfo.: | 1500 W |
![]() | Total power loss under IN: | 1,3 W |
![]() | Power dissipation per coil: | 150 mW |
![]() | Output power: | 2300 W |
![]() | Max. switching power: | 25300 W |
![]() | Conventional transformers: | 1500 VA |
![]() | Electronic transformers: | 1500 W |
![]() | C-load: | yes |
Materials
![]() | Colour: | light grey |
Dimensions
![]() | Width of rail mounted device (RMD): | 8 modules |
![]() | Height: | 90 mm |
Lighting control
![]() | Fluorescent lamps with electronical ballast (EB): | 20 x 36 W |
![]() | - uncompensated: | 1200 W |
Fluorescent bulbs control
![]() | Energy-saving lamps: | 25 x 18 W |
![]() | Power lighting fluo lamps: | 25x18W |
![]() | Fluorescent lamps parallel compensated: | 1000 W /200 µF |
LED control
![]() | Max number of LED/CFL lamps: | 25 |
![]() | 230V LED lamps: | 25 x 18 W |
![]() | Power LED: | 450 W |
![]() | LED: | Status LED integrated in manual operation button |
Incandescent bulbs control
![]() | Max. power with incandescent lamps: | 2300 W |
![]() | 230 V incandescent lamps and halogen lamps: | 2300 W |
Connection
![]() | Connection cross-sect. flexible conductor: | 0,5 / 4mm² |
![]() | Connection cross-sect. rigid cable: | 0,5 / 6mm² |
![]() | Type of load: | C-Load |
![]() | Conductor cross-section (flexible): | 0,75…2,5 mm² |
![]() | Conductor cross-section (rigid): | 0,75…2,5 mm² |
![]() | Type of contacts: | 16F |
![]() | Type of connection: | with screw |
![]() |
| |
![]() |
| |
![]() |
|
Settings
![]() | Supported configuration modes: | easy, system |
![]() |
|
Scope of delivery
![]() | Bus connection included: | yes |
Equipment
![]() | Number of outputs: | 16 |
![]() | Modular expandability: | no |
![]() | Different phases connectable: | yes |
![]() | With slide for manual switch: | yes |
Use
![]() | Differentiation characteristic 3 - Sales: | with screw terminals |
Safety
![]() | Protection index IP: | IP20 |
Use conditions
![]() | Operating temperature: | -5…45 °C |
![]() | Storage/transport temperature: | -20…70 °C |
Identification
![]() | Device family: | TXM |
![]() | Main design line: | KNX |